WARNING
Check all pipe connections, internal and external, for
gas leaks using a non-corrosive leak detection fluid.
To reduce the risk of explosion or fire, DO NOT USE
AN OPEN FLAME TO CHECK FOR GAS LEAKS! Gas
connections should be checked daily for leakage.
W924
Gas Supply Pipe Sizing and Looping
TMB2126N_SVG
1
2
3
4
5
6
7
8
9
M
6
8
7
4
5
3
2
1
9
10
11
12
1.
Gas furnace [120,000 Btu/hr. [127 Mj/hr., 35 kW]]
2.
Gas water heaters [400,000 Btu/hr. [422 Mj/hr., 117 kW] each]
3.
Gas space heaters [70,000 Btu/hr. [79 Mj/hr., 21 kW] each]
4.
Sediment traps, supply pressure taps and shut-off valves. Refer to
Figure 1
.
5.
1 in. [25 mm] gas pipe loop
6.
19 ft. [5.8 m]
7.
Minimum Pipe Size is 3/4 NPT for 120 Series Gas, 1 NPT for 170 and 200 Series Gas
8.
25 ft. [7.6 m]
9.
Main regulator
10.
Gas meter
11.
Pressure regulator (if required)
12.
120 series tumble dryers = 270,000 Btu/hr. [285 Mj/hr.,79 kW] each; 170 series tumble dryers = 395,000 Btu/hr. [417 Mj/hr.,
116 kW] each; 200 series tumble dryers = 425,000 Btu/hr. [448 Mj/hr., 125 kW] each
Figure 15
SAMPLE CALCULATIONS:
Equivalent length = Total length of main gas supply pipe to
the far end of the tumble dryers.
= 25 ft. + 19 ft. [7.6 m + 5.8 m] gas supply pipe
= 44 ft. [13.4 m] Total Gas Line
Total Btu/hr. = The sum of the Btu/hr. of all 120 series tumble
dryers being fed by the main gas supply pipe.
= 9 x 270,000 [285, 79]
= 2,430,000 Btu/hr. [2,564 Mj/hr., 712 kW]
Using
Table 4
, the main supply pipe diameter should be 3 NPT.
IMPORTANT: Gas loop piping must be installed as il-
lustrated to equalize gas pressure for all tumble dryers
connected to single gas service. Other gas using appli-
ances should be connected upstream from loop.
Gas Requirements
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
42
Part No. 70532501ENR7