Installing Your PanelView 1200 Terminal
Chapter 3
3-11
Figure 1.12
Color Touch Screen Terminal Dimensions
21191
0.680"
(17.27 mm)
13.50"
(342.90 mm)
13.80"
(350.52 mm)
0.520"
(13.21 mm)
15.305"
(388.75 mm)
0.400"
(10.16 mm)
12.40"
(314.96 mm)
PanelView
Color
Touch Screen
Installation Notes
PanelView 1200 terminals are installed in a rectangular cut-out in a panel.
Depending on the model, the terminals mount with mounting studs or
mounting clips.
With the stud-mount models (TA4, TC4, KA1, KC1) nuts are provided
with the terminal. A gasket is fixed on the faceplate. Tighten the terminal
down onto the enclosure to compress this gasket. The gasket has built-in
spacers that will not allow it to be over-compressed. You will notice that
the tightening torque increases significantly when you reach the correct
compression. At this point the tightening torque should not exceed 10
inch-pounds.
With the clip-mount touch screen terminals (TA1, TC1), four mounting
clips are provided. Assemble the mounting clips before installing the
terminal.
Use a screwdriver to install two clips on each side. (See Figure 1.16.)
Tighten the screws until the chassis is held snugly in place against the
panel. A torque of 10 inch-pounds provides a good seal. Do not
over-tighten the screws.
PanelView 1200 Terminal
Cutouts
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com