Troubleshooting
Appendix B
B-7
Error code
What to do
Probable causes
180
Timed out, 1771 backplane module not
responding"
PLC controller in program mode, or PanelView
1200 terminal in configuration mode.
The PassThrough block transfer assignment in
the PanelView 1200 terminal doesn't match the
PassThrough block transfer assignment in the
application file being downloaded.
Put the PLC controller and the PanelView 1200
terminal in run mode.
Match the address assignments.
186
ACK timeout"
Remote I/O cables are disconnected.
Noisy line.
The computer's address is the same as the PLC
station address, when using a KT or KT2 device.
Ensure that both ends of the Remote I/O cables
are connected and terminated according to the
baud rate used.
Reassign the KT or KT2 address.
190
All others"
Programming terminal is not connected to Data
Highway Plus network.
Connect programming terminal to Data Highway
Plus network.
208
Error Opening Network"
Wrong KT2 driver card location. The switch
settings on the KT2 card don't match the
settings entered in the PassThrough download
configuration.
Ensure that the settings on the KT2 card match
those entered in the PassThrough download
configuration.
211
Bad configuration file format"
Trying to download through a PLC5/40 where
the PanelView 1200 terminal is assigned a rack
number greater than 7.
The switch settings on the KT card don't match
the settings entered in the PassThrough
download configuration.
Use PanelBuilder software 4.00.02 or higher.
Ensure that the settings on the KT card match
those entered in the PassThrough download
configuration. See the following table for
information on selecting a memory location for
the KT card.
218
FID mismatch detected"
A rack was configured in the PanelBuilder
application that is not an actual PanelView
terminal rack.
Reassign the correct terminal rack using
PanelBuilder software.
221
Unknown external error received from 6200
library"
Screen objects have addresses assigned to the
PassThrough block transfer file.
The PLC controller or the PanelView 1200
terminal don't have an 82ohm resistor when
running at 230K baud on Remote I/O.
The PassThrough block transfer file in the
PanelBuilder application is also being used on a
BTR or BTW instruction in the PLC controller.
Assign a different address to the PassThrough
block transfer file, or assign different addresses
to the screen objects.
Install 82ohm resistor.
Assign a unique address to the PassThrough
block transfer file.
224
Communications board address incorrect"
PanelView 1200 rack assignment is greater than
7.
The KT card bit pattern doesn't match the
jumper setting on the KT card.
Use PanelBuilder software 4.00.02 or higher.
Ensure that the settings on the KT card match
those entered in the PassThrough download
configuration. See the following table for
information on selecting a memory location for
the KT card.
For help on solving PanelBuilder software problems, see your
PanelBuilder Development Software User Manual or your PanelBuilder
1200 Configuration Software for Windows User Manual.
PanelBuilder Problems
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com