Specifications
Appendix A
A-5
This RS-232 port can either be connected to the development system and
used to upload/download application files, or it can connected to a printer
and used to print screen images, reports, or alarm messages. You can
assign separate port settings for each of these purposes. The applicable port
settings are used automatically.
The following table lists the port settings.
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19.2 kilobaud
Parity Types
Odd, Even, None
Stop Bits
1, 2
Data Bits
7, 8
Handshake
Hardware, Software (XON, XOFF), None
Auto Line Feed*
Off, On
Auto Form Feed*
Off, On
*
Printer only these two parameters cannot be turned On for the serial port.
The factory defaults are the same as the default settings that the
development software will apply to the selected RS-232 port on your
development system, so you normally shouldn’t need to change them. The
factory defaults are as follows:
Port Parameters
Upload/Download
Printer
Baud Rates
9600
9600
Parity Types
None
None
Stop Bits
1
1
Data Bits
8
8
Handshake
Hardware
Software
Auto Line Feed
Off (not configurable)
On
Auto Form Feed
Off (not configurable)
On
Refer to the following table for information on AC power.
Power Supply Type
Switching
Range
90-132, 180-264 VAC
automatic setting by the PanelView 1200 terminal to match
available power supply
Frequency Range
47-63 Hz
Power Consumption
Color Terminal
80 W
Monochrome terminal
50 W
While the color terminal degausses, there is a 6.5 amp surge. The surge
lasts less than 400 milliseconds.
Serial Communications Port
AC Power