The optional Remote Keyswitch Assembly is a mode select keyswitch and
an RS-232 port that can be mounted on the front of an equipment panel for
easier access. For complete mounting instructions, refer to Publication
2711-5.2, Remote Keyswitch and RS-232 Port Assembly for PanelView
Terminals.
The following diagram shows the Remote Keyswitch Assembly cutout.
Figure 1.20
Remote Keyswitch Assembly Cutout
2.625"
(66.67 mm)
20184
∅
0.187" (4.75 mm)
4 Places
∅
3.000
(76.2 mm )
+0.025"
0.000
2.625"
(66.67 mm)
+0.64 mm
0.00
The Upload/Download Cable is used to transfer an application file to or
from a PanelView 1200 terminal. As marked, one end of the cable connects
to your development system computer’s RS-232 port. The other end
connects to the PanelView 1200 terminal’s RS-232 port.
The Upload/Download cable by itself can be connected to a computer with
a 25-pin, RS-232 port (most XT
computers). Both a 25- to 9-pin adapter
and a specially marked short cable are provided with each
upload/download cable. You will need these adapters only for the
following cases:
Remote Keyswitch Assembly
Dimensions
Upload/Download Cable