Troubleshooting
Appendix B
B-5
Problem
What to do
Cause
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
While trying to download an application file, a
PROBLEM window appears stating: Error code
208 was returned by the PassThrough Utility".
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
The PassThrough Utility has been unable to
establish DH+ communications with the PLC5.
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Make sure the Programming Terminal DH+
Address" and the PLC DH+ Address" are
properly assigned.
Make sure that you have selected the proper
DH+ Hardware Driver" for your system, and that
the DH+ Driver Card Location" code is correct.
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁÁÁ
Immediately after completing a PLC5
PassThrough Download, a Minor Fault Status
bit is set in the PLC5.
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁÁÁ
The rack assignment configuration of the
application file downloaded to the PanelView
1200 terminal did not exactly match the
application file that was overwritten.
ÁÁÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
Á
ÁÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁÁÁÁÁ
Use the PLC5 6200 Series software to clear the
Minor Fault; then reconfigure the PLC5 to
recognize the new rack assignment.
PLC Controllers Required for PassThrough
Important
Only specific models and revisions of PLC controllers are
capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.
Processor
Series
Revision
Valid PLC Racks
Baud Rates
PLC5/11
All
All
3 octal
57.6 kbps
115.2 kbps
230.4 kbps
PLC5/15
B
N or later
1-3 octal
57.6 kbps
PLC5/20
All
All
13 octal
57.6 kbps
115.2 kbps
230.4 kbps
PLC5/25
A
J or later
1-7 octal
57.6 kbps
PLC5/30
A
B or later
1-7 octal
57.6 kbps
115.2 kbps
230.4 kbps
PLC5/40
A
B
E or later
B or later
1-17 octal
57.6 kbps
115.2 kbps
230.4 kbps
PLC5/60
A
B
E or later
B or later
1-27 octal
57.6 kbps
115.2 kbps
230.4 kbps
PLC5/250
All
All
1-37 octal
57.6 kbps
115.2 kbps
230.4 kbps