PanelView 1200 Terminal Functions
Chapter 2
2-14
Pressing the Center Screen button sets the screen alignment to its default
position. Pressing the Save & Exit button saves the current alignment and
returns you to the Configuration Mode Menu.
The following figure shows the Screen Alignment screen for a touch
screen terminal.
20156
ALIGN SCREEN
Center
Screen
Up
Down
Test
Alignment
Left
Right
Save &
Exit
Stuck Button/Cell Timeout
Choose Stuck Button Timeout or Stuck Cell Timeout from the
Configuration Mode menu to set the length of time a touch cell or function
key may be pressed before the terminal determines that it (the key or cell)
is stuck and enters fault mode.
Use the keypad to set the amount of time from 0 to 99 seconds. A setting
of 0 disables the function.
False Depression Test (Touch Screen Only)
Choose False Depression Test on touch screen terminals to check for any
“false depressions” of touch cells caused by hardware problems or by
excessive vibration or noise in the terminal’s environment. The test
identifies the number of false depressions detected and the number of the
last cell that was detected as pressed. Up to 100 false depressions can be
registered on any one test. The test should run for several hours while
vibration and/or noise are present.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com