Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
145
Troubleshooting
Appendix
B
0xF27z
(2)
Recoverable A non-recoverable communication fault has
occurred on the expansion I/O module.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Replace the slot number z module.
0xF28z
(2)
Recoverable Expansion I/O baudrate error.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Replace the slot number z module.
0xF29z
(2)
Recoverable A module fault is detected on your expansion I/O
module.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Replace the slot number z module.
0xF2Az
(2)
Recoverable Expansion I/O power failure
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Replace the slot number z module.
0xF2Bz
(2)
Recoverable Expansion I/O configuration fault.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Correct the expansion IO module configuration in the user program
to match that of the actual hardware configuration.
•
Check the expansion I/O module operation and condition.
•
Replace the expansion I/O module.
0xF300
Recoverable The memory module is present but memory
module is empty and restore operation is
requested.
Perform the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Check to make sure there is a valid project in the memory module.
•
Download a user program and use the backup function to the
memory module.
0xF301
Recoverable The memory module’s project is not compatible
with the controller.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Check to make sure there is a user program with a controller that
has the correct controller catalog configured.
•
Download a user program and use the backup function to the
memory module.
0xF302
Recoverable The password is mismatched between memory
module and controller. Only applies to Micro820
controller when Remote LCD performs the restore
operation.
This fault does not apply to Micro800 controller
firmware revision 10 and later.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 149
.
•
Check to make sure that the user program in the memory module
has the correct password.
•
Download a user program with a password and use the backup
function to the memory module.
•
Use Connected Components Workbench to enter the correct
password into the controller and perform the restore operation
again.
0xF303
Recoverable The memory module is not present and restore
operation is requested.
Check to make sure the memory module is present.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...