58
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Chapter 5
Communication Connections
Here are some configuration examples based on the limits described in the table
above:
1.
The maximum number of drives that can be controlled over EtherNet/IP
is 16. This is due to the maximum limit of TCP Client connections is 16,
and the maximum limit of EtherNet/IP Client connections is also 16.
2.
If you have 10 devices controlled over EtherNet/IP, the maximum number
of devices that can be controlled over Serial is six. This is due to the
maximum limit of Client connections is 16.
3.
The total number of UDP sockets plus TCP Client/Server sockets has a
maximum limit of eight.
Connection Limits for Micro820 Controllers
Description
Connections
CIP Connections
Total number of client plus server connections
24
Maximum number of client connections for all ports
16
Maximum number of server connections for all ports
24
Maximum number of EtherNet/IP connections
Client
16
Server
24
Maximum number of USB connections
Client
–
Server
Maximum number of serial connections
Client
16
Server
24
TCP Connections
Total number of client plus server connections
64
Maximum number for EtherNet/IP
Client
16
Server
16
Maximum number for Modbus TCP
Client
16
Server
16
Maximum number for User Programmable Sockets
8
User Programmable Sockets
Total number of User Programmable Sockets
(any combination of UDP plus TCP Client/Server)
8
TIP
The 2080-REMLCD USB uses the CIP serial server connections for
embedded serial port.
IMPORTANT
If all client/server connections are fully loaded, performance may be
affected, such as data loss and intermittent delays during
communication.
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...