144
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
Appendix B
Troubleshooting
0xF023
Non-
recoverable
The controller program has been cleared. This
happened because:
•
a power down occurred during program
download or transfer from the memory
module.
•
the Flash Integrity Test failed (Micro810 only).
Perform one of the following:
•
Corrective Actions for Non-recoverable Faults on page 149
•
Download or transfer the program.
0xF030
0xF031
0xF032
0xF033
Recoverable Power down information in persistent memory
may not be written properly due to a noisy
environment or an internal hardware failure.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
See
Corrective Actions for Recoverable Faults on page 149
.
0xF050
Recoverable The embedded I/O configuration in the user
program is invalid.
See
Corrective Actions for Recoverable Faults on page 149
.
0xF100
Recoverable There is general configuration error detected in
the motion configuration downloaded from the
Connected Components Workbench software,
such as number of axis, or motion execution
interval being configured out of range.
Perform the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Correct the axes configuration in the user program.
0xF110
Recoverable There is motion resource missing, such as
Motion_DIAG variable not defined.
Perform the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Correct the axes configuration in the user program.
0xF12z
(1)
Recoverable Motion configuration for axis z cannot be
supported by this controller model, or the axis
configuration has some resource conflict with
some other motion axis, which has been
configured earlier.
Perform the following:
•
Corrective Actions for Recoverable Faults on page 149
•
Remove all axes and re-configure motion with the guidance from
the User Manual.
0xF15z
(1)
Recoverable There is a motion engine logic error (firmware
logic issue or memory crash) for one axis
detected during motion engine cyclic operation.
One possible reason can be motion engine data/
memory crash.
See
Corrective Actions for Recoverable Faults on page 149
.
0xF210
Recoverable The expansion I/O terminator is missing.
Perform the following:
1. Power off the controller.
2. Attach the expansion I/O terminator on the last expansion I/O
module on the system.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page 149
0xF230
Recoverable The maximum number of expansion I/O modules
has been exceeded.
Perform the following:
1. Power off the controller.
2. Check that the number of expansion I/O modules is not more than
four.
3. Power on the controller.
4. See
Corrective Actions for Recoverable Faults on page 149
0xF250
Recoverable There is a non-recoverable error and the
expansion I/O module(s) could not be detected.
See
Corrective Actions for Recoverable Faults on page 149
.
0xF26z
(2)
Recoverable An expansion I/O master fault is detected on the
system.
See
Corrective Actions for Recoverable Faults on page 149
.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...