Chapter 4
Wire Your Controller
To convert this resistance into a temperature, use the following Steinhart-Hart
equation:
Where
:
Coefficients a, b, and c are provided by the thermistor manufacturer.
Calibrate Thermistor
1.
Connect a resistor (10 K
Ω
is recommended) across Vref and Analog
Input 00 of your Micro820 controller following the diagram,
. The resistor is measured as Ri using a precision
multimeter.
2.
Calculate the ideal counts (C1) for resistor (Ri) following this equation:
C1 = 14.14 K
Ω
/ (14.14 K
Ω
+ Ri) * 4095
3.
Read the actual counts (C2) of Analog Input 00 from Connected
Components Workbench.
4.
Calculate for calibration Gain.
Gain = C1/C2
For example
:
If Ri is measured as 10.00 K
Ω
, then
C1 = 14.14 / (14.14 + 10.00) * 4095 = 2399 counts;
C2 is read from Connected Components Workbench as 2440; so
Gain = 2399/2440 = 98% .
5.
In Connected Components Workbench, go to Embedded I/O
configuration page. Change the Gain parameter value for Input 00 to 98.
No changes are required to the Offset parameter value.
6.
Repeat the same steps to calibrate all the other analog input channels.
=
T
1
a + bln(R) + c[ln(R)]
3
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...