Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
137
Specifications
Chapter
A
Environmental
Specifications
Time (msec)
Data Payload
28-characters
502-characters
518-characters
1028-characters
1493-characters
3676-characters
Average write time
per data log including
all overheads
Average write time
excluding first sample
Average write time
excluding all
overheads
2900
2400
1900
1400
900
400
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding
air, max
65 °C (149 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN mount: 25 g
PANEL mount: 45 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...