Chapter 4
Wire Your Controller
2080-LC20-20QBB / 2080-LC20-20QBBR
DC Sinking Input Configuration – Inputs 00...11
IMPORTANT
Note the following:
•
The “-DC24” terminals on the Input (terminal 2) and Output (terminals
2 and 3) Terminal Blocks are internally shorted.
•
“NU” means that the terminal is not used / no connection.
•
Inputs I-00, I-01, I-02, and I-03 are shared between digital and analog
inputs.
•
Inputs I-00, I-01, I-02, and I-03 can only be used in sinking input
configuration.
•
I-00 to I-03 are non-isolated input channels, do not connect -DC24
(Input terminal 2) to Earth/Chassis ground.
•
Do not connect -DC24 (Output terminal 2) to Earth/Chassis Ground.
-DC24
+DC10
I-00
I-01
I-02
I-03
COM0
I-04
I-05
I-08
I-07
1
2
3
4
5
6
7
8
9
10
11
12
+DC24
-DC24
VO-0
-DC24
NU
+CM0
O-00
O-01
O-03
O-02
+CM1
-CM0
1
2
3
4
5
6
7
8
9
10
11
12
I-10
I-09
NU
I-11
13
14
15
16
O-05
O-04
-CM1
O-06
13
14
15
16
I-06
46211
Input Terminal Block
Output Terminal Block
-DC24
+DC10
I-00
I-01
I-02
I-03
COM0
I-04
I-05
I-08
I-07
1
2
3
4
5
6
7
8
9
10
11
12
+DC24
-DC24
VO-0
-DC24
NU
+CM0
O-00
O-01
O-03
O-02
+CM1
-CM0
1
2
3
4
5
6
7
8
9
10
11
12
I-10
I-09
NU
I-11
13
14
15
16
O-05
O-04
-CM1
O-06
13
14
15
16
I-06
-DC b
-DC a
+DC a
+DC b
+DC c
-DC c
-DC d
CR
CR
CR
+DC d
-24 VDC
+24 VDC
N
L
L1
L2
2080-PSAC12W
Summary of Contents for 2080-LC20-20AWB
Page 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Page 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Page 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Page 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...