Troubleshoot the FLEX I/O
Analog I/O Modules
What This Chapter Contains
Read this chapter to troubleshoot your I/O module.
Status Indicators
1794-IE8H Module
The 1794-IE8H module has one power indicator that is on when power is
applied to the module and one status indicator for each input.
For Information On
See Page
Status Indicators
6-1
Repair
6-2
Chapter Summary
6-2
Table 6.1 1794-IE8H Status Indicators
Indicator
Color
State
Meaning
Status
Red
On
At power up – Channel 0 indicator lights at powerup until
all internal diagnostics are checked. After successful
powerup, the indicator goes off if no fault is present.
After successful powerup – Indicates a critical fault
(diagnostic failure, etc.)
Blinking (when
faults are
enabled, and bit
set)
Indicates a noncritical channel fault
Yellow
On/blinking
HART device was found on the associated channel (when
configured)
Power
—
Off
Module not powered
Green
On
Module receiving power
Blinking
No flexbus communication
A = Status indicators
B = Insertable labels for writing individual input
designations
C = Power indicator
PWR
1794-IE8H
8 CH HART ANALOG INPUT
IN1
IN0
IN2
IN3
IN4
IN5
IN6
IN7
3
A
B
C
I/O
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......