Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
F-7
Analog Output Data
Input
Refer to the following tables for input information.
Diagnostic Status Data
HART Rebuild Bit
The HART rebuild bit is
[Adapter Name]:[Slot]:I.Data[0].7.
Channel
Bits
0
[Adapter Name]:[Slot]:O.Data[1]
1
[Adapter Name]:[Slot]:O.Data[2]
2
[Adapter Name]:[Slot]:O.Data[3]
3
[Adapter Name]:[Slot] O.Data[4]
4
[Adapter Name]:[Slot]:O.Data[5]
5
[Adapter Name]:[Slot]:O.Data[6]
6
[Adapter Name]:[Slot]:O.Data[7]
7
[Adapter Name]:[Slot]:O.Data[8]
Diagnostic Description
Bit 3
Bit 2
Bit 1
Bit 0
Normal
0
0
0
0
Calibration Failure
0
0
0
1
Configuration Failure
0
0
1
0
Message Failure
0
0
1
1
Lead Break Detection
0
1
0
0
EEPROM Failure
0
1
0
1
RAM Failure
0
1
1
0
ROM Failure
0
1
1
1
Calculation Failure
1
0
0
0
Data Out of Range
1
0
1
1
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......