1
Publication 1794-UM063A-EN-P - March 2006
Appendix
D
FLEX I/O HART Modules Network Messaging
What This Appendix
Contains
This appendix discusses:
•
How to communicate with the FLEX I/O HART modules via the MSG
or CIO instruction
•
The differences between Attributes and Assembly Indexes
•
Enhancements to the HART frame
Communication
The messaging between the processor and the HART I/O module is handled
via MSG or CIO instructions, depending on the processor type. These ladder
logic instructions need specific details for proper operation. In particular, they
need four items:
•
Class
The Class value for FLEX is 7D hex.
•
Instance
The Instance is a number between 1 and 8. This number indicates the
module location relative to the adapter module. Use 1 for the module
connected directly to the adapter.
•
Service
The Service value is 0E hex for Get Attribute Single and 10 hex for Set
Attribute Single. Use a Service value of 0E hex to read data from the
adapter and 10 hex to write data to the adapter.
•
Attribute
The Attribute value is based on the Attribute Values table.
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......