Publication 1794-UM063A-EN-P - March 2006
Additional HART Protocol Information
C-7
Universal Commands
Table C.5 Universal Commands
Command
Data in Command
Data in Reply
#
Function
Byte
Data
Type
Byte
Data
Type
0
Read unique
identifier
—
None
—
0
254 (expansion)
—
1
Manufacturer
identification code
2
Manufacturer device
type code
(1)
3
Number of preambles
required
4
Universal command
revision
5
Device-specific
command revision
6
Software revision
7
Hardware revision
8
Device function
flags
(2)
(H)
9…11
Device ID number
(B)
1
Read primary
variable
—
—
—
0
PV units code
—
1…4
Primary variable
(F)
2
Read current and
percent of range
—
None
—
0…3
Current (mA)
(F)
4…7
Primary variable
3
Read current and
four (predefined)
dynamic variables
—
None
—
0…3
Current (mA)
—
4
PV units code
5…8
Primary variable
9
SV units code
10…13 Secondary variable
(3)
14
TV units code
15…18 Third variable
19
FV units code
20…23 Fourth variable
6
Write polling
address
0
Polling address
—
—
As in command
—
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......