Publication 1794-UM063A-EN-P - March 2006
5-8
Calibrate Your Module
1794-IE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, for example, 0x03 >
channel 0 and 1 have to be calibrated.
Table 5.8 1794-IE8H Calibration Item Byte Value Identifier List
Identifier (Decimal)
Value
Access Rule
0
Offset channel 0
Read/write
…
…
…
7
Offset channel 7
Read/write
8
Gain channel 0
…
…
…
15
Gain channel 7
Read/write
16…47
Reserved
—
48
Status mask offset
Read/write
49
Status mask gain
50
Calibration day
51
Calibration month
52
Calibration year
53
Checksum over calibration
values
Read
54…255
Reserved
—
7
6
5
4
3
2
1
0
Calibrate Channel 0
:
Calibrate Channel 1
Calibrate Channel 7