
Publication 1794-UM063A-EN-P - March 2006
E-4
Configure the 1794-IE8H Module in RSLogix 5000 Software Over the ControlNet Network
Filter Cutoff
The generic profile sets all of the filter bits to 0, which is an invalid value. You
must set these bits to a valid value or you will get a diagnostic error value of 2.
Channel
Bits
0…3
[Adapter Name]:[Slot]:C.Data[0].5
[Adapter Name]:[Slot]:C.Data[0].6
[Adapter Name]:[Slot]:C.Data[0].7
4…7
[Adapter Name]:[Slot]:C.Data[1].5
[Adapter Name]:[Slot]:C.Data[1].6
[Adapter Name]:[Slot]:C.Data[1].7
Filter Cutoff Bits
Description
7
6
5
0
0
0
Not Valid
0
0
1
Not Valid
0
1
0
Not Valid
0
1
1
10 Hz (100 ms)
1
0
0
4 Hz (250 ms)
1
0
1
2 Hz (500 ms)
1
1
0
1 Hz (1 s)
1
1
1
0.5 Hz (2 s)
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......