Publication 1794-UM063A-EN-P - March 2006
C-8
Additional HART Protocol Information
11
Read unique
identifier associated
with tag
0…5
Tag
(A)
0…11
As Command 0
—
12
Read message
—
None
—
0…23
Message (32
characters)
(A)
13
Read tag descriptor,
date
—
None
—
0…5
Tag (8 characters)
(A)
6…17
Descriptor (16
characters)
(A)
18…20 Date
(D)
14
Read PV sensor
information
—
None
—
0…2
Sensor serial number
—
3
Units code for sensor
limits and minimum
span
4…7
Upper sensor limit
(F)
8…11
Lower sensor limit
12…15 Minimum span
15
Read output
information
—
None
—
0
Alarm select code
—
1
Transfer function code
2
PV/range limits code
3…6
Upper range value
7…10
Lower range value
11…14 Damping value
(seconds)
(F)
15
Write protect code
16
Private-label
distributor code
16
Read final assembly
number
—
None
—
0…2
Final assembly
number
—
17
Write message
0…23
Message (32
characters)
(A)
—
As in command
—
18
Write tag descriptor,
date
0…5
Tag (8 characters)
(A)
—
As in command
—
6…17
Descriptor (16
characters)
18…20 Date
(D)
19
Write final assembly
number
0…2
Final assembly
number
—
—
As in command
—
(1)
Bit 2 = protocol bridge device.
(2)
Bit 0 = multisensor device, bit 1 = EEPROM control required.
(3)
Truncated after last supported variable.
Table C.5 Universal Commands
Command
Data in Command
Data in Reply
#
Function
Byte
Data
Type
Byte
Data
Type
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......