About the FLEX I/O HART Analog Modules
What This Chapter Contains
Read this chapter to familiarize yourself with the input and output analog
modules.
What the FLEX I/O Analog
I/O Modules Do
The 1794 HART input and output modules must be used in a ControlNet or
EtherNet network.
The 1794-IE8H module accepts up to 8 analog inputs. The inputs are
nonisolated and will accept current in either of the following two ranges: 4 to
20 mA or 0 to 20 mA. The default input range is 0 to 20 mA. The inputs have
both fixed hardware filters and selectable firmware digital filters.
Similarly, the 1794-OE8H module provides as many as 8 analog outputs. The
outputs are nonisolated and will provide current in either of the following two
ranges: 4 to 20 mA or 0 to 20 mA. The default output range is 0 to 20 mA.
Each module offers:
•
local microprocessor intelligence for advanced features.
•
full functionality without switches or jumpers.
•
multiple data ranges that can be independently programmed
in channel groups.
•
lead breakage detection.
•
overrange/underrange alarms.
•
remote transmitter alarm.
For Information About
See Page
What the FLEX I/O Analog I/O
Modules Do
1-1
How FLEX I/O Analog Modules
Communicate with Programmable
Controllers
1-2
Physical Features of Your Analog I/O
Module
1-3
Chapter Summary
1-8
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......