Publication 1794-UM063A-EN-P - March 2006
Additional HART Protocol Information
C-9
Common Practice
Commands
Table C.6 Common Practice Commands
Command
Data in Command
Data in Reply
#
Function
Byte
Data
Type
(5)
Byte
Data
Type
(5)
33
Read transmitter
variables
—
None
(2)
—
0
Transmitter variable
code for slot 0
—
1
Units code for slot 0
2…5
Variable for slot 0
(F)
6
Transmitter variable
code for slot 1
—
7
Units code for slot 1
8…11
Variable for slot 1
(F)
12
Transmitter variable
code for slot 2
(6)
—
13
Units code for slot 2
14…17 Variable for slot 2
(F)
18
Transmitter variable
code for slot 3
—
19
Units code for slot 3
20…23 Variable for slot 3
(F)
34
Write damping value 0…3
Damping value
(seconds)
(F)
—
As in command
(F)
35
Write range values
0
Range units code
—
—
As in command
(F)
1…4
Upper range value
(F)
—
5…8
Lower range value
(F)
36
Set upper range
value (push SPAN
button)
—
None
—
—
None
—
37
Set lower range
value (push ZERO
button)
—
None
—
—
None
—
38
Reset configuration
changed flag
—
None
—
—
None
—
39
EEPROM control
0
(1)
EEPROM control code
—
—
As in command
—
40
Enter/edit fixed
current mode
0…3
Current (mA)
(3)
(F)
—
As in command
—
41
Perform device
self-test
—
None
—
—
None
—
42
Perform master
reset
—
None
—
—
None
—
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......