Calibrate Your Module
Table 5.11 1794-OE8H Interpretation of Calibration Data Structure Content During Read Access (Idle Status)
Command Byte
Item Byte
Data1 Byte
Data2 Byte
Status (Binary)
Command Bits 0…5 (Decimal)
00
Idle
0
Nothing is done. The state after power on.
0
0
0
1
The min scale value is supported at the outputs according
to channel-mask
Channel-mask
2
The max scale value is supported at the outputs
according to channel-mask
3
The written min scale value of Current was accepted
Value
low-byte
Value
high-byte
4
The written min scale value of Voltage was accepted
5
The written max scale value of Current was accepted
6
The written max scale value of Voltage was accepted
7
Reserved
(1)
Reserved
(1)
Reserved
(1)
Reserved
(1)
8
All calibration values are set to default
0
0
0
9
The specified calibration value is set to default
Value-identifier
10
Reserved
(2)
Reserved
(2)
Reserved
(2)
Reserved
(2)
11
Reserved
(2)
12
Reserved
(2)
13
Reserved
(2)
14
The calibration content is saved to EEPROM.
0
0
0
(1)
Do not use. Designated for future use.
(2)
Reserved. Used during manufacture of the product.
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......