Configurable FLEX I/O Analog Module Features
2-11
Fault Alarm
Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100 Hz (10 ms) filter for wire off or lead break detection.
Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.
10
Not Assigned
11
D/A count
as 0…20
mA
0.28% of
0…20 mA
0…22 mA
0…8000
(0…22 mA)
363
Min=0 mA
Max=22 mA
Hold
last=hold
50%=11 mA
12
4…20 mA
—
—
Not assigned
—
—
—
13
% as
4…20 mA
0.16% of
4…20 mA
3…21 mA
-625 …+10625
(2’s complement)
(-6.25…+106.25
%)
625
Min=3 mA
Max=21 mA
Hold
last=hold
50%=12 mA
14
% as
4…20 mA
0.16% of
4…20 mA
2…22 mA
-1250…+11250
(2’s complement)
(-12.50…+112.5
0%)
625
Min=2 mA
Max=22 mA
Hold
last=hold
50%=12 mA
15
Not Assigned
Table 2.4 1794-OE8H Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
Output = 22
datatable
(
8000
)
Output = 16
datatable
(
10000
)
+ 4
Output = 16
datatable
(
10000
)
+ 4
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......