Publication 1794-UM063A-EN-P - March 2006
Input, Output and Configuration Files for the Analog I/O Modules on the ControlNet Network
4-7
Device Actions
Device actions include:
•
Communication fault behavior
•
Idle state behavior
•
Input data behavior upon module removal
Communication Fault Behavior
You can configure the response to a communication fault for
each I/O module in its system. Upon detection of a communication fault,
the module can:
•
Leave the module output data in its last state (hold last state)
•
Reset the module output data to zero (reset)
•
Apply fault state data to the module output
Idle State Behavior
The FLEX I/O HART module can detect the state of the controlling
processor or scanner. Only 2 states can be detected: Run mode, or Program
mode (idle).
When Run mode is detected, the adapter copies the output data received from
the processor to the corresponding module output. When Program mode is
detected, the I/O module can be configured to:
•
Leave the module output data in its last state (hold last state)
•
Reset the module output data to zero (reset)
•
Apply fault state data to the module output
Summary of Contents for 1794-IE8H
Page 1: ...FLEX I O HART Analog Modules 1794 IE8H and 1794 OE8H User Manual...
Page 6: ......
Page 12: ...Publication 1794 UM063A EN P March 2006 Table of Contents 6...
Page 60: ...Publication 1794 UM063A EN P March 2006 3 14 Install Your FLEX I O Analog Modules...
Page 88: ...Publication 1794 UM063A EN P March 2006 5 20 Calibrate Your Module Notes...
Page 92: ...Publication 1794 UM063A EN P March 2006 A 2 Specifications Notes...
Page 114: ...Publication 1794 UM063A EN P March 2006 C 16 Additional HART Protocol Information Notes...
Page 145: ......