Appendix C
PowerMonitor 500 EtherNet/IP Device Profile
Get Attribute Single Service
The Get Attribute Single service returns the single attribute that is specified by
the parameter Attribute ID.
The following example shows how to create your message instruction
configuration for the Get Attribute Single Service type for the Logix Designer
application. In this example, we read the Instance 102 attributes of the Assembly
Object.
Parameter
Choice
Notes
Message Type
CIP Generic
Service Type
Get Attribute Single
Service Code
e (hex)
e = Get Attribute Single
Instance
102
This parameter is the Assembly Instance of the specific
data table to be read. In this example, 102 = Real-time
Power, PF, Frequency
Class
4 (hex)
4 = Assembly Object
Attribute
3 (hex)
3 = Data
4 = Size of data
Source Element
N/A
Not applicable to a Read
Source Length
N/A
Not applicable to a Read
Destination Element
See Notes
This element is the first element of the controller tag that
stores the data being read. The tag is an array of the
applicable data type the same length as the Attribute. In
this example, the tag is an array of 18 REAL elements.
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......