Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
81
PowerMonitor 500 EtherNet/IP Device Profile
Appendix C
Assembly Object Instances
The communication module Assembly Object supports nine instances (instances
100d to 108d). The Data attributes of these instances can be accessed via Class 1
scheduled connections and via Class 3 or UCMM unscheduled connections.
PowerMonitor 500 EtherNet/IP Device Profile
for more
information on the content of the Assembly Instances.
Assembly Object Services
Assembly Instance
Size (No. of elements)
Data Type
Data Table Description
100
20
UINT
Product Information
101
12
REAL
Real-time Voltage and Current
102
18
REAL
Real-time Power, PF, Frequency
103
12
REAL
Max Voltage and Current
104
17
REAL
Max Power, PF, Frequency
105
12
REAL
Demand Voltage and Current
106
17
REAL
Demand Power, PF, Frequency
107
18
REAL
Energy Meters
108
2
UINT
Alarm and Output Status
Service Code
Class/Instance Usage
Service Name
0x0E Class/Instance
Get
Attribute
Single