Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
69
Technical Specifications
Appendix B
kWh pulsating
0.001 kWh/kVARh by pulse if the Ct ratio by VT ratio is
≤
7
0.01 kWh/kVARh by pulse if the Ct ratio by VT ratio is
≥
7.1
≤
70.0
0.1 kWh/kVARh by pulse if the Ct ratio by VT ratio is
≥
70.1
≤
700.0
1 kWh/kVARh by pulse if the Ct ratio by VT ratio is
≥
700.1
≤
7000
10 kWh/kVARh by pulse if the Ct ratio by VT ratio is
≥
7001
≤
70.00k
100 kWh/kVARh by pulse if the Ct ratio by VT ratio is >70.01k
Max frequency: 16 Hz, according to EN50470-1
Rear position Status Indicators
On the base
Green as power-on
On communication modules
Two status indicators: one for TX (green) and one for RX (amber)
Key-pad
For variable selection, programming of the instrument working parameters, ‘dmd’, ‘max’, total energy, and partial energy
Reset
Table 40 - Display, Status Indicators, and Commands
Attribute
Value
Table 41 - Main Functions
Attribute
Value
Password
Numeric code of max four digits; two protection levels of the programming data
1st level
Password ‘0’, no protection
2nd level
Password from 1…9999, all data are protected
System selection
System 3P.n unbalanced load
3-phase (4-wire Wye)
System 3P unbalanced load
3-phase (3-wire) Delta
Three currents and three line-to-line voltage measurements
For ARON connection, two currents (with special wiring on screw terminals) and three line-to-line voltage
measurements.
System 3P.1 balanced load
3-phase (3-wire), one current and three line-to-line measurements.
3-phase (4-wire), one current and three line-to-neutral voltage measurements.
System 3P.2 balanced load
3-phase (2-wire), one current and one line-to-neutral (L1) voltage measurement
System 2P
2-phase (3-wire) Split-phase
System 1P
1-phase (2-wire) Single phase
Transformer ratio
VT (PT)
1.0…999.9 / 1000…9999
CT
1.0…999.9 / 1000…9999 (up to 50 kA in case of CT with 5 A secondary current)
Filter
Operating range
Selectable from 0…100% of the input display scale
Filtering coefficient
Selectable from 1…256
Filter action
Measurements, analog signal retransmission, serial communication (fundamental variables: V, A, W, and their derived
ones)
Displaying
Number of variables
Up to five variables per page. See
Front Panel Features on page 11
. Seven different set of variables available according to
the application being selected. See
Backlight
The backlight time is programmable from 0 (always on) to 255 minutes
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......