Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
19
Installation and Wiring
Chapter 2
Wiring Diagrams
The PowerMonitor™ 500 unit can monitor various three-phase, single-phase, and
split-phase circuits. Select the voltage connections, current wiring, and system
metering mode to match the configuration of the circuit being monitored.
provides a key for you to select the proper wiring diagrams and system
metering modes.
The wiring diagrams in this manual are drawn with U.S. (NEMA) conventions.
For convenience, a connection diagram is shown in IEC style on the left and in its
corresponding NEMA style (used in the U.S.) on the right.
Figure 10 - Wiring Diagram Interpretation
Table 4 - Wiring Diagram Explanation
Circuit type
No. of CTs
No. of PTs
Wiring Diagram
System
Configuration
3-phase, 4-wire Wye Unbalanced load
3
-
3P.n
3
3
3-phase, 2-wire Wye Balanced load
1
-
3P.2
1
1
3-phase, 3-wire Delta Unbalanced load
3
-
3P
2
-
Open Delta Unbalanced load
3
2
3P
2
2
Open Delta Balanced load
1
2
3P.1
3-phase, Single CT Balanced load
1
-
3P.1
1
3
Split-phase
2
-
2P
2
2
Single phase
1
-
1P
1
1
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......