Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
13
PowerMonitor 500 Unit Overview
Chapter 1
Display Features
Figure 2 - Features
Display Icons
Alarm Icons
•
Indicates a high value alarm
•
Indicates a low value alarm
ROW
1
ROW
2
ROW
3
ROW
4
ROW
5
1
2
3
4
5
10
9
6
7
11
8
12
Display Item
Description
1
Phase displacement indicator: inductive L, -L, or capacitive C, -C.
The sign is based on the direction of real power flow.
Positive = consuming power, negative = generating power.
See the
Geometric Representation of Power and Power Factor
in
for more information.
In Programming mode, the indicator displays E when a parameter can be edited.
2
Indicates the measured value phase (line-to-neutral L1 or line-to-line L12).
3
Indicates the measured value phase (line-to-neutral L2 or line-to-line L23).
4
Indicates the measured value phase (line-to-neutral L3 or line-to-line L31).
5
Engineering unit and multiplier indicator (k, M, V, W, A, var, PF, Hz, An).
6
ALR: the alarm display function is active. PROG: the programming function is active.
7
Area set aside for energy counters (see
Table 1
), text messages, date and time (format: dd.mm.yy/hh:mm).
8
Indicates that metering values are dmd (demand) or MAX (maximum) values.
Display Item
Description
9
Indicates that the metering values displayed are system (three-phase) values.
10
Indicates a phase sequence error alarm for Voltage rotation.
11
Configuration lock switch is not active. Always indicates unlocked.
12
Indication of serial RS-485/RS-232 data transmission (TX) and reception (RX).
9
10
11
12
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......