66
Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
Appendix B
Technical Specifications
Current overloads
Continuous
6 A, at 50/60 Hz
For 500 ms
120 A, at 50/60 Hz
Voltage overloads
Continuous
1.2 × V
nom
(where V
nom
is the nominal voltage of the module)
For 500 ms
2 × V
nom
(where V
nom
is the nominal voltage of the module)
Input impedance
400VL-L (V2)
> 1.6 M
Ω
208VL-L (V1)
> 1.6 M
Ω
5(6)A <
0.2VA
Frequency
40…440 Hz
Table 35 - Input Specifications
Attribute
Value
Table 36 - Pulse (digital) Output Specifications (P option)
Attribute
Value
Physical outputs
2
Purpose
For either alarm output or digital output
Type Relay,
SPDT
type:
•
AC 1-5 A at 250V AC
•
AC 15-1.5 A at 250V AC
•
DC 12-5 A at 24V DC
•
DC 13-1.5 A at 24V DC
Configuration
Use the front keypad
Function
The outputs can work as alarm outputs but also as digital outputs, communication controlled outputs, or in any other
combination
Alarms
Up alarm and down alarm that is linked to the virtual alarms, for other details, see
Response time, min
≤
200 ms, filters excluded. Set-point on-time delay: ‘0 s’
Pulse
Signal retransmission
Total: +kWh, -kWh, +kVARh, -kVARh. Partial: +kWh, -kWh, +kVARh, -kVARh
Pulse type
The listed variables can be connected to any output
Pulse duration
Programmable from 0.001…10.00 kWh/kVARh per pulse.
≥
100 ms <120 ms (ON),
≥
120 ms (OFF),
according to EN62052-31
Communication controlled outputs
The activation of the outputs is managed through the serial communication port
Insulation See
Table 44
Isolation Between Inputs and Outputs (1 minute)
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......