70
Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
Appendix B
Technical Specifications
Virtual alarms
Working condition
Basic unit (indication only) or with (P) optional digital output modules
No. of alarms
Up to 4
Working mode
Up alarm and down alarm
Controlled variables
The alarms can be connected to any instantaneous variable. See
List of Connectable Variables on page 72
Set-point adjustment
From 0…100% of the display scale
Hysteresis From
0 to full scale
On-time delay
0…9999 s
Response time, min
≤
200 ms, filters excluded. Set-point on-time delay: ‘0 s’
Reset
By using the front keypad. It is possible to reset the following data:
•
All max and dmd values
•
Total energy (kWh, kVARh)
•
Partial energy (kWh, kVARh)
Clock
Functions
Universal clock and calendar
Time format
Hour: minutes: seconds with selectable 24 hours or AM/PM format
Date format
Day-month-year with selectable DD-MM-YY or MM-DD-YY format
Battery life
Ten years
Easy connection function
For all display selections, both energy and power measurements are independent from the current direction. The
displayed energy is always ‘imported’
Table 41 - Main Functions
Attribute
Value
Table 42 - General Specifications
Attribute
Value
Temperature, operating
-25…40 °C (-13…104 °F) (R.H. from 0…90% noncondensing at 40 °C) according to EN62053-21, EN50470-1 and
EN62053- 23
Temperature, storage
-30…70 °C (-22…158 °F) (R.H. < 90% noncondensing @ 40 °C) according to EN62053-21, EN50470-1 and EN62053- 23
Installation category
Cat. III (IEC60664, EN60664)
Insulation See
Table 44
Isolation Between Inputs and Outputs (1 minute)
Dielectric strength
4 kV AC rms for 1 minute
Noise rejection CMRR
100 dB, 48…62 Hz
EMC
According to EN62052-11
Electrostatic discharge
15 kV air discharge
Immunity to radiated electromagnetic fields
Test with current: 10V/m from 80…2000 MHz
Test without any current: 30V/m from 80…2000 MHz
Burst
On current and voltage measuring inputs circuit: 4 kV
Immunity to conducted disturbances
10V/m from 150 KHz…80 MHz
Surge
On current and voltage measuring inputs circuit: 4 kV; on ‘L’ auxiliary power supply input: 1 kV
Radio frequency suppression
According to CISPR 22
Standard compliance
Safety
IEC60664, IEC61010-1 EN60664, EN61010-1
Metrology
EN62052-11, EN62053-21, EN62053-23, EN50470-3. MID ‘annex MI-003’
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......