Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
59
PowerMonitor 500 Unit Data Tables
Appendix A
Table 29 - Configuration - Analog Outputs: Read and Write
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
304609
16
Analog output A0: parameters
configuration
CUSTOM See
304625
16
Analog output A1: parameters
configuration
CUSTOM
Table 30 - Analog Output Configuration Parameters
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
Block
a0
1
Type of the variable that is linked to
the N analog output
UINT
Block
a1
2
Minimum electric value of the N
analog output
REAL
Value min = 0
Value max = 9,999,000
Block
a3
2
Maximum electric value of the N
analog output
REAL
Block
a5
2
Minimum output value of the N
analog output
REAL
Value min = 0.0
Value max = 100.0
Block
a7
2
Maximum output value of the N
analog output
REAL
Block
a9
7 Reserved