
Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
53
PowerMonitor 500 Unit Data Tables
Appendix A
Maximum Metering Values (power, PF, frequency)
Table 17 - Table Properties
CIP Assembly Instance
104
No. of Elements
17
Length in Words
34
Data Type
REAL
Data Access
Read Only
Table 18 - Maximum Metering Values (power, PF, frequency) Data Table
Element
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
0
300361 2 Max
W
L1
REAL
1
300363 2 Max
W
L2
REAL
2
300365 2 Max
W
L3
REAL
3
300367 2 Max
W
3
REAL
4
300369 2 Max
VA
L1
REAL
5
300371
2 Max
VA
L2
REAL
6
300373 2
Max
VA
L3
REAL
7
300375 2
Max
VA
REAL
8
300377
2
Max VAR L1
REAL
Negative values correspond to lead (C), positive values correspond
to lag (L)
9
300379
2
Max VAR L2
REAL
10
300381
2
Max VAR L3
REAL
11
300383 2 Max
VAR
REAL
12
300385
2
Max PF L1
REAL
The Max PF displayed corresponds to the PF value with the largest
phase angle.
13
300387
2
Max PF L2
REAL
14
300389
2
Max PF L3
REAL
15
300391 2 Max
PF
REAL
16
300393 2 Max
Hz
REAL
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......