Publication 1394-5.0 — May 2000
Configuring Your 1394 Analog Servo System
8-19
[Rem. Data In/Out:Px]
This series of parameters represent
linkable
inputs and outputs to the SCANport "analog"
inputs and outputs for each of the six available
ports.
Parameter Numbers
58-69
Parameter Group
Linear List
Display
Units
None
Parameter Type
Read Only
Linkable
In=No, Out=Yes
[Resolvr Posn]
This parameter supplies the position feedback
count. 65,535 represents the counts per 1/2
revolution.
Parameter Numbers
216, 217, 218, 219
Parameter Group
Monitor Parms
Display Units
None
Parameter Type
Read Only
Linkable
No
[Resolvr Turns]
The number of resolver electrical turns is
supplied by this parameter. When these values
reach maximum, the value drops to -32768 and
begins to again count up and down.
Parameter Numbers
244, 245, 246, 247
Parameter Group
Monitor Parms
Display Units
None
Parameter Type
Read Only
Linkable
No
[Rg Power Usage]
Displays the present average power regenerated
by all motors back to the system module.
Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.
Parameter Numbers
40
Parameter Group
Smart Sys Data
Display Units
%
Parameter Type
Read Only
Linkable
No
[Shunt Kl]
Shunt resistor long time constant, measured in
seconds.
Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.
This parameter only needs to be configured
when you are using custom resistors.
Note: [Shunt Type] must be set to "custom shunt"
before making modifications to this shunt
parameter (44-48).
Parameter Numbers
47
Parameter Group
Linear List
Display Units
S
Parameter Type
Read/Write
Change While Running
No
Minimum Value
1
Maximum Value
255
Default Value (22 kW)
70
Default Value (5 and 10 kW
)
10
[Shunt Ks]
Shunt resistor short time constant, measured in
seconds.
Active on all Smart Power 22 kW systems and 5
and 10 kW (Series C or later) systems.
This parameter only needs to be configured
when you are using custom resistors.
Note: [Shunt Type] must be set to "custom shunt"
before making modifications to this shunt
parameter (44-48).
Parameter Numbers
46
Parameter Group
Linear List
Display Units
ms
Parameter Type
Read/Write
Change While Running
No
Minimum Value
250
Maximum Value
2550
Default Value (22 kW)
250
Default Value (5 and 10 kW
)
250
Summary of Contents for 1394 SERCOS
Page 1: ...User Manual 1394 Digital AC Multi Axis Motion Control System Catalog No 1394 50 Allen Bradley...
Page 10: ...Publication 1394 5 0 May 2000 viii Table of Contents...
Page 118: ...Publication 1394 5 0 May 2000 5 8 Wiring Your 1394 Analog Servo System...
Page 124: ...Publication 1394 5 0 May 2000 6 6 Commissioning 1394 GMC and GMC Turbo Systems...
Page 166: ...Publication 1394 5 0 May 2000 8 30 Configuring Your 1394 Analog Servo System...
Page 232: ...Publication 1394 5 0 May 2000 A 34 Specifications...
Page 292: ...Publication 1394 5 0 May 2000 D 14 Catalog Numbers...