Application Note CC-002-A
89
Figures 2A and 2B. VRLA Cells.
DUAL INTERCONNECTIONS
Figures 3A and 3B show the typical intercell connections for dual post
cells. This type of interconnection requires that two readings be taken.
The first one shown should be with the intercell leads connected from
Terminal Post A to Terminal Post C. Take the second reading with the
intercell leads connected from Terminal Post B to Terminal Post D. The
positive (a red clip) Cellcorder lead should remain connected (as shown)
to the same terminal post for both measurements.
Figure 3A. Connections for Dual Posts.