CRT-300 Setup Options
14
Default Thresholds
- If a site is selected, you can quit the site settings and
return to default thresholds for voltage, resistance, temperature, and SG
without affecting the site file.
To clear site setup and thresholds
- To have no site associated with a file
that has been linked, and to clear threshold settings, use the Clear button on
the
Active Site
screen. For a complete description, refer to
Unlinking a File
and Clearing Thresholds
.
Main Menu > CRT Setup|Thresh
To set up Cellcorder (not site file) thresholds
- Select Thresholds, then
choose Voltage, Cell Resistance, Intercell Resistance, Specific Gravity or
Temperature. A series of screens appears for parameters that may be set.
Press the Arrows to change values. Press Accept to accept the value
displayed.
Fahrenheit or Celsius
- On the Temperature screen, select Celsius or
Fahrenheit using the C/F button before setting the high/low temperatures.
Disabling a Threshold
- Setting any threshold value to zero (or 32
F / 0
C
for temperature) disables the threshold.
Use the Up-Down-Left-Right Arrows to enter threshold values. You cannot
use the keypad to type numeric values. The following table shows the ranges
for each programmable entry.
TIP
: Shift+Alrm also accesses Threshold.