securityProbe 5ESV Manual
Updated until firmware 404m
- 48 -
Recording Source:
Here you can choose either internal or external microphone.
Microphone boost (+20dB):
Boosts the microphone by 20 dB
Microphone Sensitivity:
The level of sensitivity that can be set. For example, if you set
the level to 80, then the microphone will detect more sound if the level was set a 20.
Pulse Length:
This defines the minimum duration of a sound to trigger an alert
notification.
Rearm:
The Rearm parameter is used to prevent the sensor from flickering between two
states. For example if the
Warning High
threshold for the sound sensor is set to 80 and
the sensor was to vary between 79 and 80, a very large number of emails, traps, and
events would be logged. The Rearm parameter prevents this by forcing the signal level to
drop by the Rearm value before changing the state back to normal. In this example, if
Rearm is set to 2 then the sensor would have to drop from 80 down to 77 before the
status would change from
Warning High
back to normal.
Data Collection Type:
There are 3 settings for this parameter: lowest, highest, and
average. Data will be collected for the lowest, highest, or average sound reading
accordingly.
Display Style:
Here you can choose the gauge style, or the classic bar style gauge.
Advanced Status Text and Color:
Here you can select to change your display text and
warning colors.
Note: As for all the other sensors you can now set up the sound detector to be attached to a
notification. Then when your thresholds are broken it will trigger a specified type of notification.