![Airwell DLS 30 DCI Service Manual Download Page 9](http://html.mh-extra.com/html/airwell/dls-30-dci/dls-30-dci_service-manual_2880105009.webp)
2-2
PRODUCT DATA SHEET
SM DLSDCI 3-A.1 GB
2.2 DLS 24 DCI
Model Indoor Unit
DLS 24 DCI R410A AW
Model Outdoor Unit
AWAU-YBDE024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Warmer
Capacity
(1)
kW
6.8 (1.7÷7.4)
7.6 (1.8÷8.5)
Pdesign
kW
6.8
7.5
7.5
SEER / SCOP
(1)
W/W
4.8
3.5
4.0
Energy efficiency class
B
A
A+
Annual energy consumption
kWh
1,217
4,433
2,347
Tbiv
o
C
N/A
-3
6
Tol
o
C
N/A
-15
-10
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating
A
20
INDOOR
Fan type & quantity
Centrifugal x 1
Fan speeds
H/M/L
RPM
800/670/550
Air flow
(2)
H/M/L
m3/hr
1310/1115/870
External static pressure
Min-Max
Pa
25-60
Sound power level
(3)
H/M/L
dB(A)
65/60/55
Sound pressure level
(4)
H/M/L
dB(A)
47/43/38
Moisture removal
l/hr
1.53
Condensate drain tube I.D
mm
19
Dimensions
WxHxD
mm
790x256x749
Weight
kg
31
Package dimensions
WxHxD
mm
960x300x855
Packaged weight
kg
33.5
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Twin Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
RPM
250 - 820 (continuous)
Air flow
Max.
m3/hr
2,750
Sound power level
Nom.
dB(A)
67
Sound pressure level
Nom.
dB(A)
55
Dimensions
WxHxD
mm
900x700x340
Weight
kg
61.0
Package dimensions
WxHxD
mm
985x730x435
Packaged weight
kg
63.5
Units per pallet
Units
6
Stacking height
units
2 levels
Refrigerant type
R410A
Refrigerant charge (standard connecting tubing
length)
kg(7.5m)
2.3
Additional charge per 1 meter
gr / 1m
7.5m < 0gr < 15m < 35gr per 1m < 30m
Connections between units
Liquid line
In.(mm)
3/8”(9.53)
Suction line
In.(mm)
5/8”(15.88)
Max.tubing length
m.
30
Max.height difference
m.
15
Operation control type
Remote control
Heating elements
kW
Others
(1) Rating conditions in accordance with EN14825 and EN14511 (for ducted units).
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1.4 meter distance from unit.