PERFORMANCE DATA & PRESSURE CURVES
SM DLSDCI 3-A.1 GB
5-21
PERFORMANCE DATA & PRESSURE CURVES
SM DLSDCI 2-A.5 GB
5.6
DLS 43 DCI / YBD 042 H11
5.6.1
Cooling Capacity (kW)
LEGEND
TC
–
Total Cooling Capacity, kW
PI
–
Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB
–
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.6.2
Capacity Correction Factors (Cooling)
OD COIL ENTERING AIR
DB TEMPERATURE [C0]
DATA
22/15
24/17
27/19
29/21
32/23
TC
SC
PI
TC
12.08
12.87
13.66
14.45
15.24
SC
9.85
10.05
10.25
10.45
10.65
PI
2.93
2.99
3.04
3.10
3.16
TC
11.50
12.29
13.08
13.87
14.66
SC
9.60
9.80
10.00
10.20
10.40
PI
3.27
3.33
3.39
3.44
3.50
TC
10.92
11.71
12.50
13.29
14.08
SC
9.35
9.55
9.75
9.95
10.15
PI
3.62
3.67
3.73
3.79
3.84
TC
10.34
11.13
11.92
12.71
13.50
SC
9.10
9.30
9.50
9.70
9.90
PI
3.96
4.02
4.07
4.13
4.19
TC
9.64
10.43
11.22
12.01
12.80
SC
8.80
9.00
9.20
9.40
9.60
PI
4.37
4.43
4.48
4.54
4.60
46
35
40
25
30
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
-10 - 20
(protection range)
80 - 110 % of nominal
80 - 105 % of nominal
25 - 50 % of nominal
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
20
25
30
35
40
45
Outdoor Temperature DB [deg C]
Capaci
ty Factor
5-22
PERFORMANCE DATA & PRESSURE CURVES
SM DLSDCI 2-A.5 GB
5.6.3
Heating Capacity (kW)
LEGEND
TH
–
Total Heating Capacity, kW
PI
–
Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.6.4
Capacity Correction Factors (Heating)
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
-20
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Capacity Factor
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [°C]
DATA
15
20
25
TC
8.91
8.29
7.67
PI
2.46
2.71
2.96
TC
9.92
9.30
8.67
PI
2.97
3.22
3.47
TC
10.68
10.05
9.43
PI
3.34
3.59
3.84
TC
11.05
10.43
9.81
PI
3.53
3.78
4.03
TC
11.31
10.68
10.06
PI
3.66
3.91
4.16
TC
14.62
14.00
13.38
PI
3.85
4.10
4.35
TC
15.43
14.81
14.18
PI
4.08
4.33
4.58
TC
16.24
15.61
14.99
PI
4.31
4.56
4.81
15-24
TC
(Protection Range)
PI
ID COIL ENTERING AIR DB
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
85 - 105 % of nominal
80 - 120 % of nominal
5.10
Capacity Correction Factors (Cooling)
5.11
Capacity Correction Factors (Heating)