TROUBLESHOOTING
SM DLSDCI 3-A.1 GB
13.5.9
Checking Compressor
1) Check Compressor connections - Repair if needed.
2) Check the resistance between the three phases – all three coil resistances should be the same:
UNIT
RESISTANCE
YBD036 - H11 / INV38
0.788 Ω
INV40-50 / YBD042-060 - H11
0.188 Ω
YAD036-042-060 - H13
0.44 Ω
YBD030
0.8 Ω
YBD018-024
0.9 Ω
3) Check the compressor current while operating to be the same on each wire - In case of abnormal
current (no current or excessive current), the problem could be of driver or compressor – if driver
is checked to be operating well (
13.5.5
), replace the compressor.