13-8
TROUBLESHOOTING
SM DLSDCI 3-A.1 GB
13.4.2
Outdoor unit diagnostics and corrective actions
No
Fault Name
Fault Description
Corrective Action
1
OCT short/disconnect
Thermistor not connected or
damaged
Check Thermistor
(13.5.13)
2
CTT short/disconnect
3
HST short/disconnect
4
OAT short/disconnect
5
OMT short/disconnect
6
RGT short/disconnect
7
RLT short/disconnect
8
High pressure protection
Compressor stopped due to
high pressure protection
Normally no action is required
If the problem persists for more than twice
on each hour, check for refrigerant clog.
Check the switch operation
( 13.5.14)
9
Low pressure protection
Compressor stopped due to
low pressure protection
Normally no action is required
If the problem persists for more than twice
on each hour, check for refrigerant leak.
Check the switch operation
( 13.5.15)
10
No communication to
Driver
Driver fault
Check power supply to driver
Check driver communication
( 13.5.16)
11
•
Compressor IPM
Fault
•
IPM Driver Pin
•
Compressor Current
Sensor Fault
Over current / IPM
malfunction
Check no obstruction to electrical box and
outdoor coil air inlet.
Check Compressor
(13.5.10)
12
No Water Flow (For Hydro
Units only)
NA
NA
13
Refrigerant Leakage
NA
NA
14
DC Under/over voltage
DC voltage exceeds its limit
Check if input voltage out of limit, if not
and the problem persists, replace driver.
If voltage is high/Low, shut off the power
and recommend the customer to fix the
power supply
15
AC under voltage/AC over
Voltage/Zero Crossing
AC input voltage is lower/
higher than limit
Check if input voltage is out of limit, if not
and the problem persists, replace driver.
If voltage is High/low, recommend the
customer to fix the power supply
16
Mismatch between IDU &
ODU models
Mismatch between IDU and
ODU models
Indoor unit sizes are exceeding outdoor
unit capacity, check indoor units model
plugs. Either too high or too low capacity
indoor units
Missing ODU
Configuration
ODU dip switches are not
configured correctly
Check ODU dip switch setting if correct
Undefined ODU Model
17
No Communication to IDU IDU-ODU communication
Check communication between indoor
and outdoor units
(13.5.17)
18
System Over Power
Protection – not available
-