6-4
AIRFLOW CURVES
SM DLSDCI 3-A.1 GB
6.5
DLS UNITS RANGE AIR FLOW CORRECTION FACTORS
(at nominal rating conditions — Test mode).
Air Flow Rate [% of nominal]
60%
70%
80%
90%
100%
Cooling
TC
0.88
0.91
0.94
0.97
1
SC
0.78
0.84
0.89
0.95
1
PI
0.95
0.97
0.98
0.99
1
Heating
PI
1.07
1.05
1.03
1.02
1
TC
0.90
0.92
0.95
0.97
1
* Permissible Air flow Rate - according to model Air Flow Curves