13-13
TROUBLESHOOTING
SM DL
F
1
-A.1 GB
13.5
Procedures for checking Main Parts
13.5.1
Discharge DC Voltage
13.5.2
Checking Mains Voltage
'"*'"
the system is expected. If in range, check the Power (Circuit) Breaker and look for broken or loosed
cable lugs or wiring mistakes.
13.5.3
Checking Line Filter Board
[\ *
]\ " *"*
^\ `
both
and
driver
.
j${
14.1.16
)
13.5.4
Checking Compressor Driver
In normal operation the 7-segments display is ON continuously. Even is that case, there can still be
a Hardware problem that prevents the system to perform well or at all. If no other problem is found,
replace the driver.
Check power supply to driver connected well and no burn marks on wiring.
PFC chock is connected well. Correct if needed.
Check PFC Chock (13.5.4.3). Replace chock if needed.
Check main fuse (20A). In case fuse is burnt, replace driver.
High voltage!!!
Wait for DC voltage to be discharged before
re touching any part of the driver to
avoid electric shock.
Check to ensure that DC voltage has reduced to below 50VDC, if not, keep
waiting until it does.
If all is well but still leds are OFF, Replace driver.
13.5.4.1 YBD
018-024
Summary of Contents for DLF 18 DCI
Page 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Page 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Page 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Page 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...