12.6.3 Deicing
12.6.3.1 Deicing Starting Conditions
12.6.4.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT is 8 degree lower then the ambiant temp and the minimum time from the last deicer is passed.
Case 2: OCT is 12 degree lower then the ambiant temp and 30 minutes from the last deicer wa passed.
! %+> @W&^Ð<}% >
in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time.
' @
Deicer may accure also when the unit switch to stanby and the OCT is 8 degree lower then ambiant
temperature
12.6.3.2 Deicing Protection Procedure
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
!!()
Any
T1
T2
T3
T3
T1
12
0
Threshold
max. 12 minutes
DT
OCT
^+Ñ^}Ñ=~ %^=Ñ~