12-1
@
CONTROL SYSTEM
SM DL
F
1
-A.1 GB
12.4.3 Cooling
Mode
12.4.3.1 Cooling Mode – General
¡ &WW|%[^W& !
Temp: Selected desired temperature.
¡ |W%{%Q'ºQ%^\W%[^W
Timer: Any
I-FEEL: ON or OFF
^%^%"¡
[^ %
RCT (R/C sensor) in I-FEEL mode.
c. Indoor Coil Temp is detected by ICT.
12.4.3.2 Control
Functions
a.
COMP
Operation
In general – the operation is set by the NLOAD calculation in indoor unit side.
Other rules are according to section 12.5.1
.
b.
OFAN
Operation
In normal operation OFAN operates together with the COMP.
Other rules are according to section 12.5.3
.
c.
IFAN Operation
IFAN will operate in ANY speed regardless the ICT or COMP state.
IFAN speed will be determined according to user selection or
AUTO-FAN logic (see para. 12.4.2.2)
d.
RV
is OFF during COOL mode.
e.
HEATERS
are OFF during COOL mode.
f.
PUMP
operates in cool/dry mode (see protection section 12.6.1.1).
12.4.3.3 Sequence
Diagrams
!" !^ q^ '[
0
+1
+2
+3
-3
-2
-1
(RT - SPT) [°C]
COMP
OFAN
IFAN
RV
ON
OFF
ON
OFF
OFF
ON
OFF
User Fan Speed
COMP Speed
decrease
COMP Speed
increase
OFAN Speed
decrease
OFAN Speed
increase
Very Low
Summary of Contents for DLF 18 DCI
Page 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Page 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Page 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Page 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...