12-1
CONTROL SYSTEM
SM DL
F
1
-A.1 GB
12.4.6 Dry
Mode
12.4.6.1 DRY - General
Mode: DRY
Temp: Selected desired temperature
Fan:
LOW (automatically selected by software)
Timer: Any
I-FEEL: ON or OFF
12.4.6.2 Control
function
a. COMP
Operation
In general – the operation is set by the NLOAD calculation in indoor unit side.
Other rules are according to section 12.5.1
.
b. OFAN
Operation
In normal operation OFAN operates together with the COMP.
Other rules are according to section 12.5.3
.
c. IFAN
Operation
LOW only.
d. RV
RV is in OFF state during DRY mode.
e. HEATERS
HEATERS are in OFF state during DRY mode.
f. Pump
Pump operates in cool/dry mode.
12.4.6.3 Sequence
Diagrams
" " ! &
LOW speed IFAN.
min{
! "
,127}
RAT-SPT
IFAN Low
0
#"
MaxNLOADIF1C
NLOAD
#$"
#%&"
Note 1
''#"
Note 1
NLOAD
0
Note 1
Min(ICT,ICTE)
1