12-1
<
CONTROL SYSTEM
SM DL
F
1
-A.1 GB
12.3.4.3 System operation whenever a thermistor fault occurs
#
Sensor
Single/Multi
Hydro/
Non Hydro
IDU Status
ODU Mode
Fault
indication
System
Operation
Cool
Heat
Deicer
Idle
T
echnician/
Installation
ITU
TPT
1
OAT
Any
H/NH
Any
Yes
Normal
2
OAT
Any
H/NH
Any
Yes
Stop Comp
3
OCT
Any
H/NH
Any
Yes
Normal
4
OCT
Any
H/NH
Any
Yes
Stop Comp
5
CTT
Any
H/NH
Any
Yes
Stop Comp
6
CTT
Any
H/NH
Any
Yes
Normal
7
HST
Any
H/NH
Any
Yes
Stop Comp
8
OMT
Any
H/NH
Any
Yes
Stop Comp
9
OMT
Any
H/NH
Any
Yes
Normal
10
RGT
i
/RLT
i
Multi
NH
Inactive
(Available)
Yes
Normal
11
RGT
i
/RLT
i
Multi
NH
Inactive
(Unavailable)
No
Normal
12
RGT
i
Multi
NH
Active
Yes
Normal
13
RLT
i
Multi
NH
Active
Yes
Normal
14
RGT
i
/ RLT
i
/
ICT
i
Multi
NH
Any
Yes
Normal
15
ICT
single
H/NH
NA
Yes
Stop Comp
16
ICT single
H/NH
NA
No
Normal
17
LWT single
H
NA
Yes
Stop
Comp
18
LWT
single
H
NA
Yes
Normal
19
EWT single
H
NA
Yes
Stop
Comp
20
EWT
single
H
NA
Yes
Normal
21
IRT single
H
NA
Yes
Stop
Comp
22
IRT
single
H
NA
No
Normal
12.4
Indoor Unit Control
12.4.1 Load
calculation
LOAD is calculated according to the difference between actual room temperature and user set point temperature
by PI control.
^|W[ ! " % '
scheme.
The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD
% @ % !@
NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed
Maxium NLOAD Cooling
Maxium NLOAD Heating
Low
MaxNLOADIF1C
MaxNLOADIF1H
Medium
MaxNLOADIF2C
MaxNLOADIF2H
High
MaxNLOADIF3C
MaxNLOADIF3H
Turbo
MaxNLOADIF4C
MaxNLOADIF4H
Auto
MaxNLOADIF5C
MaxNLOADIF5H
Summary of Contents for DLF 18 DCI
Page 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Page 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Page 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Page 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...