12-2
CONTROL SYSTEM
SM DL
F
1
-A.1 GB
12.6 Thermodynamic
Protections
12.6.1 IDU
Protections
12.6.1.1 Condensate Water over Flow Protection
{@ +%}%= ¡
1 – When it is shorted with P4
0 – When it is not shorted to P4
P2
P3
Level
Don’t care
1
Normal
Don’t care
0
W
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8 min
8 min
Overflow when
unit is ON
Overflow when
unit is OFF
8 min
12.6.2 ODU
Protections
12.6.2.1 Protection types
There are 2 types of protection: Thermodynamic protections and Cut-Off protection
Thermodynamic
Cut-Off protection
Compressor AC Over Current
Low Pressure Switch
Compressor DC Over Current / Driver Overload
High Pressure Switch
Heat Sink Overheating
W
Indoor Coil Overheating
Exceeding Operating Conditions
Outdoor Coil Overheating
Compressor Overheat Protection
Indoor Coil Defrost
12.6.2.2 Protection status
Thermodynamic protections are based on reducing compressor frequency when needed. The following represent the
possible protection status and their actions
Summary of Contents for DLF 18 DCI
Page 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Page 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Page 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Page 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...