Electrical Control Function
138
Electrical Control System
3.5
3.0
High
Low
1.0
Medium
1.5
For HKD,HND, Console
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-24
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
The compressor will run at corresponding frequency according to the gross amendatory capacity demand.
Frequency
COOL_F0
COOL_F1
COOL_F2
……
COOL_F15
COOL_F16
Amendatory capacity demand.
0
1
2
……
15
16
Meanwhile the maximum running frequency will be adjusted according to the outdoor ambient temp.
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
1.3.2.2 Outdoor fan running rules